Tank Area Safety
Before you open anything underground
- No ignition sources — no smoking, no sparking tools, no running vehicles over open tank access points
- Check for vapor / odor before removing lids — if you smell strong fuel vapor, stop and assess
- Cone / barricade the work area — protect yourself and the public from open holes
- Know the site map — which tank is which, where the lines run, where sensors are
- Never reach into a sump or spill bucket without looking first
Working around open containment
- PPE — gloves, eye protection. Fuel-rated if handling product.
- Keep lids off for the minimum time needed — open, do the work, close
- Don't leave open sumps/spill buckets unattended — someone will step in them
- Have absorbent material on hand for any spill or drip
- If you find product where it shouldn't be — stop, contain, document, escalate
Observe Before You Touch
Tank-side work starts with your eyes, nose, and the ATG. Know what's normal so you can spot what's not.
Walk-the-site observation
- Check the ATG first — any active alarms? Tank levels? Water levels? Sensor status?
- Walk the fill area — look at spill bucket lids. Are they damaged, displaced, or sitting in water?
- Look at the pad surface — staining, cracking, settling near tank access points?
- Check sump lids — properly seated? Damaged? Signs of water entry?
- Smell — fuel odor near any containment point is a finding that needs investigation
- Note the weather — recent heavy rain affects water intrusion in sumps and spill buckets
What you're looking for (quick list)
Normal / acceptable
- Dry sumps and spill buckets
- Intact lids, covers, and seals
- No fuel odor at containment points
- ATG showing normal status, no alarms
- Fittings and boots in good condition
Needs attention
- Water in sumps or spill buckets
- Product (fuel) in any containment area
- Damaged/missing lids or covers
- Cracked or displaced boots/fittings
- ATG fuel alarm or sensor-out alarm
- Fuel odor near containment
Spill Buckets (Fill Containment)
Spill buckets catch spills during fuel delivery. They're the most frequently inspected containment on site.
What is a spill bucket?
A containment basin around the fill pipe at the top of each underground tank. When the delivery driver disconnects the hose, any fuel that drips is caught by the spill bucket instead of going into the ground.
- Every tank fill pipe should have one
- They must hold liquid without leaking (that's the whole point)
- They need to be kept clean and dry between deliveries
Inspection (what to look for)
- Remove the lid — is the lid intact? Does it seat properly? Is it the right lid?
- Look inside — water? Fuel? Debris (leaves, dirt, trash)?
- Check the drain valve (if equipped) — is it closed? Is it leaking?
- Check the bucket walls — cracks, holes, damage?
- Check the fill pipe cap — present, sealed, correct type?
- Check the adaptor / fitting — where the fill pipe meets the bucket. Intact? Sealed?
Cleaning a spill bucket
- Remove standing water with a hand pump or absorbent
- Remove debris (leaves, dirt, rocks)
- If fuel is present — absorb it, contain it, dispose properly, and document
- Inspect the bucket condition while it's empty (easiest time to see damage)
- Replace the lid, confirm it seats properly
Sumps (Containment at Equipment)
Sumps are containment areas at STPs, under dispensers, and at pipe transitions. They catch leaks so you can find them before they reach the ground.
Types of sumps you'll see
- STP sump (turbine sump) — around the submersible pump at the top of the tank. Contains the STP, piping connections, and often a sensor.
- Dispenser sump (dispenser pan) — under the dispenser. Contains the shear valve, flex connector, and entry piping.
- Transition sump — where piping changes direction or material. Less common but still needs inspection.
- Under-dispenser containment (UDC) — some sites have a formed containment pan under the dispenser instead of a full sump.
Sump inspection (what to look for)
- Remove the lid carefully — sumps can accumulate vapors. Don't stick your face over the opening.
- Look for liquid — water? Fuel? How much? How deep?
- Check the sensor — is there a sensor in the sump? Is it positioned correctly? Is the float free to move?
- Check fittings and boots — where pipes enter/exit the sump. Boots cracked? Fittings tight?
- Check the sump body — cracks, holes, damage to the containment itself?
- Check conduit entries — electrical conduit entering the sump should be sealed. Unsealed conduit = water entry path.
Finding fuel in a sump
- Document immediately — photo of the sump condition, note which sump, how much product
- Identify the likely source — look at every fitting, connection, and seal in the sump. Where is the fuel coming from?
- Contain — absorb the fuel. Do not pump fuel-contaminated liquid onto the ground.
- Check the ATG — is there a fuel alarm for this sensor? If not, why not? (sensor out? no sensor installed? wrong threshold?)
- Escalate per procedure — fuel in containment is a reportable event at most companies
- Repair the source if you can — tighten a fitting, replace a seal, etc. If it's beyond your scope, document and escalate.
Water in a sump
Water in sumps is extremely common, especially after rain. But don't dismiss it — investigate the entry point.
- Check lid condition — damaged or poorly seated lids let rainwater in
- Check conduit seals — unsealed conduit entries are the #1 water path into sumps
- Check pipe boots — cracked or deteriorated boots let surface water in
- Check for fuel sheen — water with a rainbow sheen = fuel present. That changes the situation.
- Remove the water — hand pump or absorbent. Dispose properly.
Tank Water Removal
Water in a fuel tank is a serious issue. It causes corrosion, equipment failure, customer complaints, and can trigger ATG alarms.
How water gets into tanks
- Delivery — water in the fuel supply (rare but happens)
- Spill bucket / fill pipe — water enters through a leaking spill bucket or damaged fill cap
- Condensation — temperature changes cause moisture to form inside the tank (more common in tanks that aren't kept full)
- Containment failure — water migrating in through compromised fittings or seals at the tank top
Detecting water
- ATG high water alarm — the probe detects water at the bottom of the tank exceeding the set threshold
- ATG water level reading — check the tank status screen for current water level (even without an alarm)
- Manual stick reading with water paste — apply water-finding paste to a tank stick, lower it to the bottom, and read the color change
- Customer complaints — vehicles stalling, poor performance, water in fuel symptoms
Water removal procedure (general)
- Verify the tank and water level — ATG reading + manual stick if needed. Know how much water you're dealing with.
- Access the tank — usually through the fill pipe or a dedicated access point
- Use a hand pump or approved extraction method — lower the suction tube to the bottom of the tank
- Pump slowly — you want to remove water, not stir it up into the fuel
- Collect into an approved container — never pump onto the ground or into a drain
- Monitor what you're pulling — water first, then you'll start seeing fuel. Stop when fuel appears.
- Recheck the ATG water level — confirm the water level dropped
- Manual stick check — verify with paste that water is below acceptable level
- Document — how much water removed, before/after levels, suspected source
- Dispose of water/fuel mixture properly — per Petro Plus and local regulations
After water removal — find the source
Removing the water fixes the symptom. Finding where it came from prevents it from happening again.
- Check the spill bucket — is it holding water? Leaking into the tank?
- Check the fill cap — damaged, missing gasket, not sealed?
- Check tank top fittings — any access point on top of the tank is a potential water entry path
- Check delivery records — did water levels jump after a recent delivery?
- Check site drainage — does water pool around the fill area?
Drop Tubes
The drop tube directs fuel from the fill pipe down to the bottom of the tank during delivery, reducing turbulence and static.
What is a drop tube?
- A tube made of aluminum or other non-magnetic metal inside the fill pipe that extends to near the bottom of the tank (never PVC — drop tubes must be non-magnetic and fuel-compatible metal)
- Fuel flows down through the drop tube during delivery instead of splashing from the top
- Reduces static buildup, turbulence, and vapor generation
- The bottom of the tube sits above the tank bottom — not touching it
- Overfill prevention valves are often integrated into or near the drop tube
When you might need to pull a drop tube
- Tank cleaning — drop tube must come out for the tank to be cleaned
- Drop tube replacement — cracked, broken, or wrong-length tube
- Overfill valve service — the overfill prevention device may need inspection or replacement
- Delivery problems — driver reports slow fill rate or can't deliver (possible drop tube obstruction or collapse)
- Inspection / compliance — periodic check of drop tube condition and length
Drop tube removal (general)
- Confirm the tank — verify tank number/product. Do not pull the wrong tube.
- Barricade the area — you're about to have an open tank access
- Remove the fill cap and any spill bucket hardware as needed
- Remove the fill adapter — the threaded adapter that the delivery driver connects to. This must come out before the drop tube can be pulled. Note the adapter type and orientation.
- Note the position/orientation of the drop tube before removing — you need to put it back the same way
- Pull the tube straight up — it will have fuel on it. Have rags and a container ready.
- Inspect the tube — cracks, dents, corrosion, buildup inside, length (should reach near the tank bottom)
- Inspect the overfill valve (if present) — float condition, movement, sealing surface
- Reinstall or replace — seat properly, correct orientation, confirm it drops to the right depth
- Reinstall the fill adapter — thread it back in properly, verify it seats and seals correctly
- Reassemble remaining fill hardware — spill bucket fittings, fill cap, lid
- Document — what you found, what was replaced, tube condition
Overfill prevention basics
The overfill prevention valve (OPV) restricts or stops fuel flow when the tank reaches a set level (usually 90-95% capacity). It prevents the driver from overfilling the tank.
- Float-operated — as fuel level rises, the float restricts the opening
- If it fails open — overfill is possible during delivery. The driver's only protection is the ATG high-level alarm.
- If it fails closed / restricted — driver can't deliver fuel. Slow fill or no fill.
- Test by observation — does the float move freely? Is it stuck, corroded, or damaged?
STP (Submersible Turbine Pump) Basics
The STP is the pump that pushes fuel from the tank to the dispensers. Understanding how it works helps you troubleshoot flow and pressure issues.
How an STP works (simple version)
- The STP sits inside the tank, submerged in fuel, inside the STP sump at the tank top
- An electric motor spins an impeller (the functional element) that pushes fuel up through the piping to the dispensers
- Fuel is pressurized in the line — typically 25-30+ PSI at the dispenser
- The STP runs on demand — when a dispenser is activated, the STP starts and pressurizes the line
- A check valve at the STP outlet holds line pressure when the pump is off
Common STP brands
- Red Jacket — very common. Uses a "functional element" (impeller assembly) that is a frequent service item. Typically fixed-speed with a standard contactor/capacitor setup.
- FE Petro (Franklin Fueling) — also widely used. Many FE Petro STPs are variable speed, controlled by a MagVFC (Variable Frequency Controller). The MagVFC adjusts motor speed to maintain target line pressure. See the MagVFC section below for troubleshooting.
- Both brands: the motor sits on top in the sump, the pump/impeller is below in the tank, and the riser pipe connects them.
STP symptoms you'll encounter
- STP not running — check power (breaker, contactor, wiring), check if the dispenser is actually calling for fuel
- STP running but low pressure — worn functional element, air in the line, check valve not sealing
- STP cycling on/off — possible leak in the line, failing check valve, or leak detector issue
- STP running continuously — possible leak downstream, bad pressure switch, or control issue
- Noisy STP — cavitation (air), worn bearings, loose mounting. Document what you hear.
STP electrical basics
- Most STP motors run on 208V (single-phase or three-phase depending on the site and motor type)
- Fixed-speed STPs (Red Jacket, older FE Petro): typically use a contactor and a single capacitor to start and run the motor
- Variable-speed STPs (FE Petro VS2/VS4): controlled by a MagVFC — no traditional contactor/capacitor. The MagVFC is the controller, motor starter, and speed regulator all in one.
- Check the contactor (fixed-speed) — pitted contacts, stuck open or closed, coil not energizing
- Check the capacitor (fixed-speed) — swollen, leaking, or failed capacitor prevents the motor from starting or running properly
- Check wiring in the sump — water intrusion causes corrosion on motor leads and connections
FE Petro MagVFC (Variable Frequency Controller)
The MagVFC controls variable-speed FE Petro STPs (PMA VS2 and VS4 models). It adjusts motor speed to maintain target line pressure. This section covers status codes, alarm codes, DIP switch settings, and troubleshooting — all from the Franklin Fueling Systems installation manual.
Display status codes (normal operation)
These are NOT alarms. They indicate normal MagVFC operating states.
| Display | Meaning |
|---|---|
| Id | Idle — no hook signal present, PMA not running, no faults |
| xx : yy | Software revision (shown at power-on / reset). If display stops on yy, check for low incoming voltage or loose input power connections. |
| Pr : NN | Pressure regulate — MagVFC is running and maintaining NN psi (Pr and the number flash alternately) |
| PL | Power limit — MagVFC is running at maximum power output (demand exceeds regulate setting) |
| Sr | Slave running — displayed on a slave unit in Master/Slave configuration |
Alarm codes and troubleshooting
When a fault occurs, the alarm code displays and an audible alarm sounds. Press the Silence button to mute. Press and hold Silence to cycle through the last 3 faults (F0 = most recent, F1 = second, F2 = third). Press Reset to clear.
| Code | Condition | Causes & Actions |
|---|---|---|
| UL | Under-load / Tank empty |
Causes: Low fuel level, obstruction on PMA intake, SW3 Pole 6 set wrong for the motor connected. Actions: 1) Press Reset. 2) If fault clears, verify normal operation. 3) Check SW3 Pole 6 matches motor HP (OFF=VS2, ON=VS4). A VS2 motor with Pole 6 ON can cause false UL. 4) Check fuel level — if low, schedule delivery; reset after fuel is above PMA end bell. 5) If persistent, possible obstruction (rag/absorbent pad) on PMA inlet. |
| LI | Low incoming voltage |
Causes: Voltage fluctuations or low input voltage. Actions: 1) Press Reset. 2) If fault clears, verify normal operation. 3) Use AC voltmeter to verify incoming voltage is within 200–250 VAC. If not, contact electrician. |
| LU | Locked rotor at PMA startup |
Causes: Foreign material in PMA, defective PMA, corrosive environment (water-ballasted tank). Actions: 1) Press Reset. 2) If fault persists, lock/tag power OFF. 3) Pull the extractable — remove two 9/16" manifold bolts and the 3/4" electrical connector bolt. 4) Remove PMA end cap, try spinning rotor with 3/16" Allen wrench. If binding/damage, replace PMA (VS4 or VS2). 5) Check lead assembly wires for shorts before installing new PMA. Note: Extremely long motor wire runs or small gauge wire can cause false LU. |
| Lr | Locked rotor with PMA running |
Causes: Same as LU — foreign material or defective PMA. Actions: Same extraction/inspection procedure as LU above. Note: A partial short from a nicked pump power wire + water in conduit can show as Lr instead of SC (the MagVFC sees it as abnormally high current draw). |
| Er | Extended run |
Causes: Continuous hook signal for 60+ minutes without change in flow rate (possible stuck relay or wiring issue at dispenser). Actions: 1) Lock/tag power OFF. 2) Measure voltage across hook terminals with all dispenser handles off — should be 0V. If voltage is present, there's a wiring problem. Contact electrician. |
| SU | Upper rail short |
Causes: Short circuit in field wiring or internal MagVFC component failure. Actions: 1) Press Reset. 2) If fault recurs, lock/tag power OFF. 3) Disconnect BLK, ORG, RED wires at MagVFC motor terminals, cap each with wire nuts. 4) Power on — if display shows OC (open circuit), the short is in the field wiring to the pump. If it still shows SU, contact Franklin Fueling technical support. |
| rI | Voltage unbalance / capacitor bank |
Causes: Unbalanced incoming voltage, sudden large load, or failed MagVFC capacitor bank. Actions: 1) Press Reset. 2) Check incoming voltage and electrical loading. 3) Observe for ~10 minutes. If fault recurs, contact Franklin Fueling technical support. |
| OS | Over speed |
Causes: MagVFC operating outside frequency range. Actions: 1) Press Reset. 2) If fault persists, power down completely, wait 30 seconds, power back on. 3) If fault recurs, contact Franklin Fueling technical support. |
| OC | Open circuit (MagVFC to motor) |
Causes: Broken connection between MagVFC and PMA. Actions: 1) Press Reset. 2) If fault persists, lock/tag power OFF. 3) Disconnect motor wires at MagVFC. 4) Ohmmeter across motor wire pairs — correct reading: 1.2 ±1Ω for VS4, 2.5 ±1Ω for VS2. Any pair to ground should be open circuit. 5) If readings are wrong, continue testing at the extractable junction box to isolate where the break is — wiring, connectors, or PMA itself. Note: Extremely long wire runs or small gauge can cause false OC. |
| SC | Short circuit |
Causes: Short in wiring from MagVFC to PMA, or SW3 Pole 6 set wrong. Actions: 1) Press Reset. 2) Check SW3 Pole 6 — a VS4 motor with Pole 6 OFF (2hp setting) can cause false SC. 3) If fault persists, lock/tag power OFF. 4) Disconnect motor wires, ohmmeter test same as OC procedure. Any wire pair to ground should read >80kΩ. 5) If shorted, test at extractable junction box to isolate location. Replace PMA or wiring as needed. |
| HO | High temperature |
Causes: Excessive operating temperature inside MagVFC enclosure. Actions: 1) Verify the fan is running — replace fan if not (Part #223919930). 2) Check for excessive ambient heat where controller is mounted. 3) Verify all ventilation louvers are clear. 4) If persistent, contact Franklin Fueling technical support. |
SW1 — Pressure select (rotary switch)
The rotary switch sets the target operating pressure. Position 4 (32 psi) is the factory default and a good starting point for calibration.
| Position | Pressure |
|---|---|
| 0 | 24 psi |
| 1 | 26 psi |
| 2 | 28 psi |
| 3 | 30 psi |
| 4 | 32 psi (factory default) |
| 5 | 34 psi |
| 6 | 36 psi |
| 7 | 38 psi |
| 8 | 40 psi |
| 9 | 42 psi |
SW3 — Configuration DIP switches
Factory defaults shown in bold. Lock/tag power OFF before changing any switch.
| Pole | ON | OFF |
|---|---|---|
| 1 | Mechanical leak detectors (factory default) | Some electronic line leak detection systems. Required OFF for Veeder Root PLLD. |
| 2 | Gasoline (factory default) | Diesel product. Important — gasoline and diesel have different specific gravity, affects pressure regulation. |
| 3 | Master controller (Master/Slave setups) | Stand-alone operation or Slave (factory default) |
| 4 & 5 |
Pipe compensation (both ON = factory default). Adjust based on piping restriction: ON/ON = 0 (least restrictive) • ON/OFF = 1 • OFF/ON = 2 • OFF/OFF = 3 (most restrictive) Example: 2" fiberglass <150' = least restrictive. 1.5" convoluted flex >75' = most restrictive. |
|
| 6 | PMA VS4 motor (4hp) | PMA VS2 motor (2hp) (factory default). Incorrect setting causes false SC or UL codes. |
| 7 | Auto-reset of Under Load fault (resets automatically when tank is refilled) | Must press Reset button to clear UL fault (factory default) |
| 8 | Alternating Circuit mode (see Master/Slave section) | OFF (factory default) |
SW6 — Additional configuration switches
| Pole | ON | OFF |
|---|---|---|
| 1 | Disable Extended Run alarm | Extended Run alarm active (factory default) |
| 2 | Master/Slave fault shutdown — alarm on ANY controller shuts down ALL controllers. Required for VR PLLD. | Alarm shuts down only the faulted controller (factory default) |
| 3 | IST-VFC Compatibility Mode — for communicating with older IST-VFC units in Master/Slave (requires software v1.18+) | Native MagVFC Master/Slave communication (factory default) |
| 4 | Alternate submersibles every 30 minutes during continuous hook signal (helps keep tanks balanced at busy sites). Requires software v1.22+. | OFF (factory default) |
| 5 | Slave turn-off — when demand drops to single-pump level, slave shuts off to save energy. Requires software v1.23+. | Standard Master/Slave — slave only turns off when hook signal goes low (factory default) |
| 6–8 | Not used. Leave in OFF position. MagVFC may operate unpredictably if any of these are ON. | |
Master/Slave and Alternating Circuit configurations
When two FE Petro STPs share the same product line, the MagVFC supports three operating modes:
- Master/Slave — Master turns on first. When demand increases (more nozzles open), Master calls the Slave to assist. Slave only runs when requested.
- Alternating Circuit — Controllers rotate which one turns on each time the hook signal activates. Only one runs at a time.
- Master/Slave + Alternating — Combination of both. The first-on controller rotates, and additional controllers are called when demand increases.
SW2 — Address switches (Master/Slave)
Master = all SW2 poles OFF. Slaves are addressed per the table below. Up to 31 slaves supported.
| Address | Pole 1 | Pole 2 | Pole 3 | Pole 4 | Pole 5 |
|---|---|---|---|---|---|
| Master | Off | Off | Off | Off | Off |
| Slave 1 | On | Off | Off | Off | Off |
| Slave 2 | Off | On | Off | Off | Off |
| Slave 3 | On | On | Off | Off | Off |
| Slave 4 | Off | Off | On | Off | Off |
| Slave 5 | On | Off | On | Off | Off |
| Slave 6 | Off | On | On | Off | Off |
| Slave 7 | On | On | On | Off | Off |
| Slave 8 | Off | Off | Off | On | Off |
Pattern continues for Slaves 9–31 using binary addressing across all 5 poles.
Wiring quick reference
Motor terminals
- Labeled: GND, BLK, ORG, RED
- Match colors to pump wires — wrong polarity = motor runs in reverse (low pressure ~17–29 psi VS4, ~10–18 psi VS2)
- If pressure is suspiciously low on new install, swap any two motor wires and retest
Input power terminals
- Labeled: GND, L1, L2, L3
- 200–250 VAC, 50 or 60 Hz
- VS2: single-phase OK (L1 and L2)
- VS4: three-phase required for full performance (single-phase = VS2-level output)
- Max draw: 18A single-phase, 20A three-phase
Hook terminals
- 110 VAC or 240 VAC dispenser signal + neutral
- No polarity requirement
- No hook signal should be present when powering on the MagVFC
Motor resistance (ohmmeter check)
- VS4: 1.2 ±1 Ω between any two motor leads
- VS2: 2.5 ±1 Ω between any two motor leads
- Any motor lead to ground: should be open circuit (>80k Ω)
Max wire run (motor wiring)
| Wire gauge | Max distance |
|---|---|
| 10 AWG | 650 ft |
| 12 AWG | 400 ft |
| 14 AWG | 250 ft |
Exceeding max wire run can cause false OC or LU codes.
MagVFC replacement parts
| Part | Part Number |
|---|---|
| Fan assembly | 223919930 |
| User interface board | 225040930 |
| Normally open relay | 228289930 |
| Window lens | 402623930 |
Vapor Recovery Basics
Not all sites have vapor recovery, but where it exists, you need to know what it is and how it affects the system.
What is vapor recovery?
- Stage I — during fuel delivery. Vapors displaced from the tank during filling are captured back into the delivery truck instead of venting to the atmosphere.
- Stage II — during dispensing. Vapors from the customer's vehicle tank are captured at the nozzle and returned to the underground tank.
- The goal is to prevent fuel vapors (volatile organic compounds) from escaping into the air
- Required by regulation in many areas — varies by state and local rules
How it affects your work
- Extra piping — vapor return lines run alongside product lines. Know which is which.
- Vapor recovery nozzles/hoses — have a vapor return path built in. Heavier and more complex than standard nozzles.
- Dispenser impact — a blocked or failed vapor path can cause nozzle shut-off problems (customer complaint: "it keeps clicking off")
- Vent pipes — the tank vent system interacts with vapor recovery. Blocked or restricted vents cause tank breathing problems.
- Pressure/vacuum in the tank — vapor recovery affects tank pressure balance. ATG may show pressure/vacuum readings.
Containment Testing (Awareness)
Containment (sumps and spill buckets) must be tested periodically to prove it can hold liquid. This section covers awareness — not the full testing procedure.
Why containment gets tested
- Regulations require proof that sumps and spill buckets are liquid-tight
- Testing frequency varies by jurisdiction (often every 3 years, but check local rules)
- A containment that can't hold liquid defeats its purpose — leaks go to the environment instead of being caught
- Failed tests require repair or replacement before the containment can be considered compliant
What testing looks like (general)
- Hydrostatic test — fill the sump or spill bucket with water to a specified level and monitor for a set time period. If the level drops, it failed.
- Vacuum test — seal the containment and pull a vacuum. If the vacuum holds, the containment is tight.
- Specific test methods and pass/fail criteria depend on the equipment manufacturer and local regulations
- Testing requires documentation: test method, results, date, tester, pass/fail
Your role as a field tech
- Visual inspection matters — if you see obvious damage (cracks, holes, separated joints), note it. That containment will likely fail a test.
- Don't ignore findings — water or fuel in containment that shouldn't be there is a clue about integrity
- Document what you see — your inspection notes help the testing team focus on problem areas
- Know what's been tested — check site records. If a sump or spill bucket hasn't been tested in years, flag it.
Closeout (Before You Leave)
- All lids and covers are back in place and properly seated
- All barricades/cones are removed from areas you've cleared
- No open sumps, spill buckets, or tank access points left unattended
- ATG status rechecked — alarms resolved or documented with explanation
- Any fuel or water removed is properly contained and disposed of
- Work area is clean — no tools, rags, or debris left behind
- Write clear notes: what was found, what was done, and final status
- Before/after photos (wide shot of the area + close-ups of specific findings)
Goal: the next tech can understand the situation in 30 seconds from your notes and photos.