ATG Field Cheat Sheet

TLS-450PLUS + TLS-350 • alarms, sensor locating, PLLD/line tests, and site mapping.

Best practice: Screenshot first → verify physically → fix one thing at a time → recheck status → document clearly.
Workflow

60-Second Triage

Do this first

  1. Active vs. history (Is it happening now?)
  2. Identify object: Tank # / Line # / Sensor ID / Input
  3. Capture evidence: alarm screen + detail screen
  4. Classify: Containment/Sensor • Line/PLLD • Tank • System/Setup
  5. Go physical: verify in the field (don’t diagnose from the screen only)

Minimum documentation

  • Site + date/time
  • Tank/Line/Sensor ID (exact)
  • What you found (facts)
  • What you did (actions)
  • Final status (normal? still alarm?)
  • Before/after photos (screen + physical location)
Quick Reference

Common Alarms (Meaning + First Moves)

These are the alarms you meet most often, with the first moves for each. For a console alarm that is not on this page, the full Veeder Root reference covering the TLS-300, TLS-350, TLS-450, TLS-450 PLUS and TLS4 is at thrasherapps.com/droptubebuilder/reference, with the likely cause and the checks to make in order for each alarm. It is kept current there.

Keep your response consistent: confirm the device, go physical, document evidence, and recheck status.

Fuel Alarm

Meaning: Fuel/liquid detected in a space it’s not allowed (sump, dispenser pan, interstice, etc.).

  • Use sensor ID + location label + site map to go to the correct containment area.
  • Verify: active leak vs spill vs intrusion vs residual product.
  • Clean/contain per Petro Plus procedure and check likely entry points (fittings, boots, conduit, lids, seals).
  • Document: what was present, suspected cause, and what was corrected.
Safety: If you suspect an active leak, treat it as a hazard. Make safe, escalate, document.
Low Pressure Alarm

Meaning: Dispense pressure is below expected during dispensing (often line/hydraulics/power related).

  • Determine scope: one dispenser/position, one line, or multiple.
  • Check obvious causes: STP performance/power, filters, line restrictions, leaks, air, dispenser symptoms.
  • Pull PLLD/line diagnostics history for that line before repeating tests.
  • Document observed symptoms at the dispenser (slow flow, no flow, cycling, etc.).
Gross Line Fail (3.0) / Line Leak Shutdown

Meaning: Gross leak test category failure (3.0) or related shutdown condition for a line.

  • Pull PLLD diagnostics for the affected line (recent pass/fail timestamps).
  • Confirm the line and affected dispensers match the site map.
  • Verify physical conditions: obvious leaks, STP issues, dispenser symptoms.
  • Document clearly and follow company escalation if shutdown/critical.
0.2 / 0.1 Test Fail (Periodic / Annual)

Meaning: Precision line test category fail (0.2 periodic / 0.1 annual).

  • Pull 0.2/0.1 diagnostics history first; confirm which line is failing and when.
  • Consider traffic reality: precision tests need stable conditions; repeated interruptions create confusion.
  • Verify physically: leaks, seepage, check valves, fittings, dispenser symptoms.
  • Document: what the console reported + what you verified onsite.
Sensor Out Alarm

Meaning: Sensor not reporting correctly (disconnected, damaged, wiring issue, or setup mismatch).

  • Confirm the sensor exists at that location (site map) and is the correct type for that spot.
  • Inspect: wiring/conduit, water intrusion, physical damage, loose connections.
  • Document before touching anything; fix physical issues if safe/authorized.
Setup Data Warning

Meaning: Configuration/setup issue or mismatch (device/tank/line/sensor setup integrity).

  • Capture screenshots showing exactly what it references.
  • Verify console labels match the physical site map (wrong mapping causes bad troubleshooting).
  • Do not change programming unless authorized; document and escalate with evidence.
High Water Alarm (Tank Water)

Meaning: Water in the tank has exceeded the high-water limit setting.

  • Screenshot water/tank status screens and note tank number.
  • Verify the correct tank/probe association (mapping errors happen).
  • Follow Petro Plus tank water procedure (removal/containment/escalation) and document before/after.
Important: Treat tank water alarms as serious. Document clearly for the office and the customer.
Field Skill

Locate the Correct Sensor (Fast Method)

Console → Field (always)

  1. From the alarm, identify Sensor ID and any location label.
  2. Use the site map to walk directly to that sump/pan/spill bucket/interstice.
  3. Verify physically: liquid present, water intrusion, damage, sensor placement, float condition.
  4. Correct the issue per procedure; avoid “random changes.”
  5. Recheck sensor status/alarm on the console and capture the “after” screen.

Best practices

  • If the location label is wrong, note it and keep the call focused on the actual problem.
  • Take a wide photo (to prove location) and a close-up (to prove condition).
  • When recurring alarms happen at the same spot, treat it as a pattern and document the likely root cause.
Tip: A clean site map + consistent naming reduces bad troubleshooting more than any “advanced” console work.
Diagnostics

PLLD / Line Tests (3.0 / 0.2 / 0.1)

Field rule: pull diagnostics/history first, then decide if you should run tests or inspect hardware.

PLLD workflow (quick)
  1. Identify the line number referenced by the alarm.
  2. Check PLLD status/diagnostics for that line (recent pass/fail + timestamps).
  3. Confirm conditions (dispensing/traffic can interfere with clean test completion).
  4. Inspect physically based on the symptom (leak, restriction, power/STP, dispenser behavior).
  5. Document and recheck status after any change.
TLS-450PLUS (touchscreen) — where to look
  • MenuDiagnosticsPLLD0.2 GPH TESTS
  • MenuDiagnosticsPLLD3.0 GPH TESTS
Best practice: Screenshot the diagnostics page for the affected line (it’s the fastest way to explain what happened).
TLS-350 (keypad) — common diagnostic steps
  1. Press MODE for DIAG MODE
  2. FUNCTION to PRESSURE LINE LEAK DIAG
  3. STEP to the screen you need (0.2 / 0.1 / 3.0)
  4. Press PRINT (if available)
What each test means (one line each)
  • 3.0 = gross leak category (big problem / high risk)
  • 0.2 = periodic precision category
  • 0.1 = annual precision category
Best Practice

Site Mapping (Tanks, Lines, Sensors)

Goal: any tech can arrive and find the right tank/line/sensor without guessing.

What every site map must include
  • Tanks: Tank #, product, probe type, notes (water history, known issues)
  • Lines: Line # to dispenser group (rough mapping is fine at first)
  • Sensors: Sensor ID + physical location name (STP sump, dispenser pan, spill bucket, interstice)
  • Emergency stops: locations + what they affect
  • Photos: 1–2 wide shots + inside each sump/pan you service
Mapping method (field)
  1. Start with tank numbers and probe locations (confirm each physically where possible).
  2. List every sensor by console ID; walk and confirm each physical location.
  3. Name locations consistently (example: “Disp 3 Pan”, “STP Sump”, “Tank 2 Interstice”).
  4. Update the map immediately when equipment is moved/replaced.
Dispensing Issue

Slow Flow (Manual Leak Detector) — Field Troubleshooting

Slow flow is commonly triggered when a manual leak detector senses a pressure drop and restricts flow to alert the site that there is a problem.

Quick workflow
  1. Determine scope: one fueling point vs all fueling points.
  2. Install a pressure gauge on the line at a shear valve.
  3. Verify running pressure, seating pressure, and hold time.
  4. Based on scope + readings, troubleshoot dispenser-side vs pump/line-side causes.
  5. Document readings and final outcome (before/after).
Pressure check (gauge at shear valve)
  • Running pressure: should be above 25 psi.
  • Seating pressure: should settle above 20 psi.
  • Hold test: should hold that seating pressure for more than 30 minutes.
Best practice: Write the numbers down (running, seating, and time held). Photos of the gauge help reduce disputes later.
If slow flow affects ONE fueling point

Most likely: dispenser-side restriction or component issue.

  • Clogged filter
  • Bad meter
  • Bad proportional valve
Best practice: Don’t jump to STP parts if only one position is affected.
If slow flow affects ALL fueling points

Possible causes: line-side issue or pump-side pressure loss.

  • Actual leak (customer may need a line leak test performed)
  • Internal pressure loss in pump head (commonly a bad functional element on a Red Jacket STP)
  • Bad check valve
  • Bad packer o-rings
  • Bad motor or capacitor
Safety: If you suspect an actual leak, treat it as a hazard. Make safe and follow Petro Plus escalation/testing procedure.
Closeout (required documentation)
  • Which dispenser(s) / fueling points were affected
  • Where the gauge was installed (which shear valve)
  • Running PSI, seating PSI, and time held
  • What was repaired/replaced
  • Final result (normal flow restored? still slow flow?)
Franklin / INCON

EVO™ 550 / 5000 (TS-550/5000 evo) Alarms

Franklin Fueling's EVO consoles group alarms by device: system/modules, tank, sensor, line leak (LS500), and TPI (the Turbine Pump Interface that reports STP-controller faults). Source: TS-550/5000 evo Operator's Guide, FFS doc 000-2171.

Working an EVO alarm
  1. Read the alarm banner — EVO alarms are plain-English names tied to a device (Tank, Sensor, Line, TPI, module slot).
  2. Print or view Alarm History — patterns matter more than single events.
  3. If the site has TPI — the console mirrors STP-controller faults (under/over voltage, pump faults). Check the Smart Controller display too; the same fault shows both places.
  4. Verify before you clear — an alarm that matches reality (real high water, real low product) is information, not a nuisance.
Common in-tank & line alarms (from the operator's guide)
AlarmMeaningFirst actions
High product levelProduct exceeded the High limit — possible near-overfill.Get an accurate stick/level; if it doesn't match the console, verify probe programming.
High water levelWater exceeded the High limit.Verify the programmed level; if water is truly high, follow site procedure and remove water.
Low low product volumeTank (or manifold) near empty.Verify volume vs. programming; schedule delivery.
Tank Delivery DetectedA delivery was detected.Only a concern if there was no delivery at that date/time.
Tank Theft DetectedProduct left the tank in Sentinel Mode beyond the theft limit.Verify the theft limit and get an accurate level vs. inventory.
Gross Leak Detected (Line)Line leak greater than 3 GPH detected.Inspect all sumps for product immediately; see the LS500 guide (FFS 000-2145).
Marginal Pass of Gross Leak TestLast gross test passed just under the 3 GPH threshold.Check sumps for any sign of leaks and run additional tests.
Pump Communication Fail (TPI)TPI lost comms with the STP controller.Check wiring and confirm the Smart Controller has power.
Under Voltage (TPI)STP controller reporting supply under 200 VAC.Meter the controller supply; correct the feed.
Full library: the complete EVO alarm list (97 alarms with recommended actions — modules, relays, sensors, LLD, and TPI) is searchable in the DropTubeBuilder app under Dispenser Error Codes → Franklin / INCON.
Standard

Closeout (Before You Leave)

  • Recheck the console status for the tank/line/sensor you worked.
  • Capture “after” evidence (screen + physical area photo).
  • Confirm the site is left clean and safe (no open sumps/pans, no tools, no trip hazards).
  • Write clear notes: what was found, what was done, and the final status.

Goal: the next tech can understand the situation in 30 seconds from your photos and notes.