Fire Alarm Panel Library

Field reference for fire alarm and life safety technicians. 56 entries, taken from the LoopWatt app.

Free offline app

These notes are the web copy of the LoopWatt reference, built for fire alarm and life safety technicians. The same library is free inside the app, with no time limit and no account, and it works with no signal.

Get LoopWatt on the App Store
These notes come from LoopWatt

Reference notes from LoopWatt, the offline field toolkit for fire alarm and life safety technicians. It works with no cell signal, because the sites do not have any.

Get LoopWatt on the App Store

Notifier#

Trouble notes

Device troubles report by loop and address with a point label

Invalid reply usually means a device answered incorrectly: check for duplicate addresses or a swapped device type

Charger and ground fault troubles are panel level events on the system trouble list

Menu concepts

Read status to view points without changing anything

History buffer holds events; walk test enabled per loop or zone

Program changes need the panel password and often VeriFire Tools on a laptop

Families

NFS and NFW series addressable panels; ONYX line. FlashScan and CLIP polling protocols.

Notifier

NO ANS#

Scope

Device

The device, module or detector, is not answering the panel's poll. The panel is calling that address and nothing is coming back.

What to check, in order

Note the loop and address from the point label; that tells you where to walk before you touch anything

Check the device is physically present and seated in its base, since a detector twisted loose during cleaning is the single most common cause

Check the address setting on the device matches what is programmed, particularly if it was recently replaced

Check for a break in the SLC between the last answering address and this one; devices downstream failing together points at the wire rather than the device

Check terminations at the device and at the previous device on the loop for a loose or backed out screw

Swap in a known good device of the same type at the same address to separate device from wiring

If several addresses in a run go quiet together, treat it as an open circuit on the SLC rather than device failures

Notifier

INVREP#

Scope

Device

The device answered, but with a reply the panel did not expect. Something is on the loop talking out of turn or answering wrongly.

What to check, in order

Check for a duplicate address first, because two devices answering the same poll is the classic cause and it produces intermittent, moving faults

Check the device type programmed against the device actually installed; a photo head in a slot programmed for a heat will reply wrongly

Check whether the device was recently replaced with a different model or FlashScan generation

Check the panel is in the correct polling protocol for the devices fitted, FlashScan against CLIP

Check for water or corrosion at the device and its base, which can corrupt the reply

Remove the suspect device and see whether the trouble follows it or stays at the address

Notifier

DIRTY 1#

Scope

Device

The detector is dirty and needs cleaning. This is an early warning, not a failure, and the panel is telling you before it becomes a false alarm.

What to check, in order

Note the address and get it on the maintenance list rather than treating it as an emergency

Check what is around that detector: recent construction, drywall dust, a kitchen, a loading dock, or a return air path

Clean the detector per the manufacturer procedure rather than blowing it out with compressed air

Run a sensitivity report after cleaning to confirm it came back into range

If the same head dirties repeatedly, the location is the problem, not the detector; consider whether the device type suits the environment

Notifier

DIRTY 2#

Scope

Device

The detector requires cleaning immediately and is a false alarm risk. Notifier escalates to this when the compensation has run out of headroom.

What to check, in order

Treat this as needing action now, because the next event may be an unwanted alarm at three in the morning

Clean or replace the head per the manufacturer procedure

Run a sensitivity report and confirm the reading is back within the listed range, since NFPA 72 requires sensitivity to be within the listed range

Record the sensitivity result, because that record is what an inspection asks for

If it returns to DIRTY 2 quickly, replace the head rather than cleaning it again

Check the environment before reinstalling, since a head that dirties fast is usually telling you about the room

Notifier

OPEN#

Scope

Device

A module has an open circuit on its supervised wiring. The supervision current cannot complete its path on that module's circuit.

What to check, in order

Identify which module and which circuit from the point label

Check the end of line resistor is present and the correct value, because a missing or wrong EOL is the most common cause

Check terminations at the module and at the last device on that circuit

Check for a device removed for service and not put back

Measure the circuit from the module with the panel connection lifted and compare against the expected EOL value

Walk the circuit for damaged cable, especially anywhere recent trade work has happened above ceilings

Notifier

SHORT#

Scope

Device

A module has a short circuit on its supervised wiring. On a notification circuit this means the appliances will not sound when called.

What to check, in order

Identify the module and circuit from the point label

Lift the circuit at the module and measure; a dead short with the circuit lifted puts the fault in the field wiring

Check for a pinched or skinned conductor at a back box, which is where most shorts are found

Check for water in a box or device, particularly on exterior or parking structure circuits

Split the circuit at a midpoint device and measure each half to halve the search area, and once a half is disconnected leave it disconnected

Check any device added or replaced recently on that circuit

Notifier

GNDFLT#

Scope

Device

A ground fault on the main or auxiliary power supply. Fire alarm circuits use two conductors with no dedicated ground, so a conductor has found an unintended path to a grounded surface.

What to check, in order

Do not leave the system impaired: notify the authority having jurisdiction and the monitoring company, place the system on test, and post a fire watch if required

Check the panel event history first to see when it started and what else happened at that time

Rule out the panel itself by disconnecting field circuits one at a time; if the trouble clears, the fault is out on that circuit

Walk the suspect circuit against the usual suspects: water at a ceiling detector, a pinched conductor at a back box, a screw driven through cable, exterior devices after rain

Split the faulted circuit at a reachable midpoint, and once a section is removed leave it removed, because faults can sit on more than one section and restoring as you go makes it look like it never clears

With the section fully isolated and all electronics removed, measure each conductor to ground with an ohmmeter before reaching for an insulation tester

Never megger a circuit with devices connected

Notifier

DISABL#

Scope

Device

The point has been disabled. Somebody took it out of service deliberately, and it is not protecting anything while it stays that way.

What to check, in order

Find out who disabled it and why before enabling anything, because it may be disabled for a reason such as construction dust

Check the panel history for when it was disabled

Check whether a fire watch or impairment procedure is in place if the point covers a required area

Enable the point once the reason is resolved and confirm it returns to normal

Record the disable and enable, since points left disabled are a common inspection finding

Notifier

ADRFLT#

Scope

Device

An address fault: a detector or sounder base address mismatch, or an incorrect addressable power supply address.

What to check, in order

Check the address set on the device against what the panel expects for that point

Check the sounder base address against its detector, since base and head addressing is a frequent source of this

Check for a duplicate address elsewhere on the loop

Check whether the device was recently swapped and the rotary switches or programming not set

Confirm the addressable power supply address if the fault points at an ACPS

Re address and confirm the point reports normally

Notifier

PSFAIL#

Scope

Device

The power supply is not working properly. Anything it feeds is at risk of dropping out.

What to check, in order

Establish what that supply feeds before anything else, because that is the scope of the impairment

Check the AC feed to the supply and the branch circuit breaker

Check the supply's own indicators and any onboard fuses

Measure the output against its rated voltage under load rather than at rest

Check for a downstream short pulling the supply down; disconnect loads one at a time

Notify the authority having jurisdiction and the monitoring company if the affected area loses protection

Notifier

CHGFLT#

Scope

Device

The power supply's battery charger is not working properly. The batteries will not be maintained, so the system's standby capability is degrading even while everything looks normal.

What to check, in order

Measure the charging voltage at the battery terminals against the manufacturer specification

Check the battery age and date code, because a failed battery can present as a charger fault

Check battery terminals and leads for corrosion and tightness

Load test or replace the batteries if they are beyond their service life, typically around five years

Recheck charging voltage with known good batteries fitted before condemning the charger

Record the battery replacement date, since standby calculations depend on it

Notifier

LO BAT#

Scope

Device

The auxiliary power supply's battery charge is low. Standby time is reduced or gone.

What to check, in order

Measure the battery voltage at the terminals and compare against specification

Check whether AC was recently lost, since batteries take time to recover after a discharge

Check the charger output, because a low battery with a healthy charger points at the battery and the reverse points at the charger

Check battery age, terminals and leads

Replace batteries as a matched pair, never one of two

Confirm the trouble clears after the charge recovers, and recheck the next day

Notifier

HI BAT#

Scope

Device

The auxiliary power supply's battery charge is too high. Overcharging cooks batteries and shortens their life considerably.

What to check, in order

Measure the charging voltage at the battery terminals against the manufacturer specification

Check the charger setting or jumper for the battery type fitted, since a setting intended for a different chemistry overcharges

Check ambient temperature at the battery location, because heat raises voltage and accelerates damage

Inspect the batteries for swelling or heat damage and replace any that are distorted

Correct the charger before fitting new batteries, or the new ones will fail the same way

Notifier

PRLOSS#

Scope

Device

An output module or sounder base has lost its power. The device is present on the loop but has no power to do its job.

What to check, in order

Identify the point and what supplies its power, which is often a separate circuit from the SLC

Check the power circuit feeding that device and its fuse or breaker

Check terminations at the device power terminals

Check whether other devices on the same power circuit are also affected, which localises it quickly

Check the supplying power supply for its own trouble

Confirm the device operates after power is restored rather than assuming it

Notifier

LO VAL#

Scope

Device

The detector chamber reading is too low, which Notifier treats as a detector malfunction rather than a clean detector.

What to check, in order

Replace or clean the head per the manufacturer procedure

Check for a head fitted to the wrong base type

Run a sensitivity report and confirm the reading returns within the listed range

Check whether the device was recently disturbed during other work

Record the sensitivity result for the inspection file

Notifier

BLOCK#

Scope

Device

Something has come between a beam detector and its reflector. Beam detectors are line of sight devices and anything crossing the path breaks them.

What to check, in order

Look along the beam path before touching the detector, because the answer is usually visible from the floor

Check for recently installed ductwork, signage, racking, decorations or a stacked pallet

Check for a lift, scaffold or scissor lift left parked in the path

Check the reflector is still square and has not been knocked or fogged

Check for condensation or dust film on the lens or reflector

Realign per the manufacturer procedure only after the obstruction is cleared

Notifier

CO EXP#

Scope

Device

The carbon monoxide sensing element in a detector has reached its expiration date. CO elements have a fixed service life and stop being listed once past it.

What to check, in order

Replace the detector or its CO element; a CO element cannot be cleaned back into service

Check the whole site for other CO heads approaching expiry, since they were usually installed together

Note that CO 6MN is the same message six months earlier and is your chance to order ahead

Record the replacement date so the next expiry is not a surprise

Confirm the point returns to normal and test per the manufacturer procedure

Notifier

LO TEMP#

Scope

Device

A Heat or Acclimate detector is reading a temperature below its rated range. Common in unheated spaces in winter.

What to check, in order

Check the actual temperature at the device location, because the message is usually accurate

Check whether the space is unheated, a freezer, a loading dock, or an attic in cold weather

Check whether heating in that area has failed, since the detector may be reporting a real building problem

Confirm the detector type is rated for the environment; a standard head in a cold space is a design issue rather than a fault

Consider a low temperature rated device if the location is legitimately cold

Notifier

AC FAILURE#

Scope

Device

An auxiliary power supply has lost its AC feed and is running on battery. The clock is now running on standby capacity.

What to check, in order

Check the branch circuit breaker feeding that supply, and check it is a dedicated circuit that has not been repurposed

Check the AC connections at the supply

Establish whether the building lost power generally or only this circuit; only this circuit points at a local fault

Check the battery condition, because standby time is only as good as the batteries

Notify the monitoring company if the outage will be prolonged

Confirm the charger begins recovering the batteries once AC returns

Notifier

AC FAIL#

Scope

System

The main power supply has lost AC. The panel is running on battery and standby time is finite.

What to check, in order

Check the dedicated branch circuit breaker for the panel first

Confirm whether the building has lost power generally or just the panel circuit

Check AC terminations at the panel

Note the time, because NFPA 72 standby requirements are expressed in hours and you need to know how long you have

Check the battery condition and age, since a panel with weak batteries will not make its rated standby

Notify the monitoring company and the authority having jurisdiction if the outage will exceed standby capacity

Notifier

BATTERY#

Scope

System

The panel reports the battery charge as either excessive or insufficient. It is one message covering both ends.

What to check, in order

Measure the battery voltage at the terminals and determine which end of the range you are at, because the fix is opposite in each direction

If low, check the charger output and whether AC was recently lost

If high, check the charger setting for the battery type fitted and the ambient temperature

Check battery age and date code; replace beyond service life rather than chasing the symptom

Replace as a matched pair and record the date

Recalculate standby capacity if the battery size has changed from the original design

Notifier

CHARGER FAIL#

Scope

System

The main power supply's battery charger has malfunctioned. The panel will run normally on AC and fail when it matters.

What to check, in order

Measure charging voltage at the battery terminals against specification

Check the batteries themselves, since a shorted cell can present as a charger fault

Check terminals, leads and fuses in the battery circuit

Fit known good batteries and recheck before condemning the charger

Treat this as urgent despite the system looking normal, because standby protection is gone

Notify the monitoring company if the fault cannot be corrected the same visit

Notifier

ANNUN x NO ANSWER#

Scope

System

The annunciator at address x is not responding. Remote annunciators are how responding fire crews read the system, so this matters beyond the panel room.

What to check, in order

Note the annunciator address and its physical location

Check power to the annunciator

Check the communication wiring and terminations at both the annunciator and the panel

Check the address setting on the annunciator matches what is programmed

Check for a duplicate address if more than one annunciator is fitted

Check whether the run passes through an area with recent construction work

Tell the fire department contact if the annunciator serving their entry point is out

Notifier

AUXILIARY TROUBLE#

Scope

System

A device connected at J6 is malfunctioning or its cable is disconnected.

What to check, in order

Check what is actually landed on J6 for this installation, since it varies by site

Check the cable is connected at both ends and undamaged

Check power to the connected device

Disconnect the device to determine whether the trouble follows it or stays at the panel

Check the panel history for when it started and what else changed

Notifier

BAT.BACKUP RAM#

Scope

System

The RAM battery backup is low. That battery preserves the panel's programming and history when power is removed.

What to check, in order

Print or export the current programming and history before doing anything, because that is what you stand to lose

Replace the RAM backup battery with the correct part

Verify programming and the event history survived the replacement

Check the date and time afterwards

Record the replacement date, since these have a predictable life

Notifier

CORRUPT LOGIC EQUAT#

Scope

System

The database holding the panel's logic equations is corrupt. Logic equations drive cross zoning, releasing and sequence of operation, so this is not cosmetic.

What to check, in order

Do not assume the system will operate as designed, because the logic that makes it do so is the thing reporting corrupt

Notify the authority having jurisdiction and the monitoring company, and consider whether a fire watch is required

Retrieve the current programming file and compare it against your record copy

Check whether a recent programming change or download preceded it

Reload the verified programming from a known good file rather than editing around the corruption

Test the sequence of operation after reloading, not just that the trouble cleared

Notifier

BASIC WALK TEST#

Scope

System

A basic walk test is in progress. This is a status message rather than a fault, but the system is not providing normal protection while it runs.

What to check, in order

Confirm somebody is actually testing, because a panel left in walk test is a real impairment

Check the monitoring company knows the system is on test

Check how long it has been running; a walk test left on overnight means the building was unprotected

Take the panel out of walk test when testing finishes and confirm it returns to normal

Record the test in the inspection documentation

Notifier

DRILL ACTIVATED#

Scope

System

A drill has been activated. Notification appliances are sounding by command rather than because of an alarm.

What to check, in order

Confirm a drill is genuinely intended before silencing anything

Check the monitoring company was notified beforehand so the fire department is not dispatched

Check the occupants have been informed if the building requires it

Restore the panel to normal when the drill ends and confirm all appliances stop

Record the drill, since evacuation drills carry their own documentation requirements

Simplex#

Trouble notes

TrueAlarm sensors report almost dirty and dirty service conditions before nuisance level

Card level troubles (loop card, NAC card) list separately from point troubles

Ground faults isolate per power supply or loop card on larger systems, which helps localization

Menu concepts

Front panel access levels gate functions; level 3 and up changes state

System reports menu prints sensitivity reports that satisfy the sensitivity test requirement

Walk test by group with or without notification

Families

4007ES, 4010ES, 4100ES addressable platforms; IDNet and MAPNET device protocols; TrueAlarm analog sensing.

Simplex

No answer#

Scope

Device

The device is not responding on its channel. The panel is polling that address and nothing comes back.

What to check, in order

Note the channel and address from the point label before walking anywhere

Check the device is present and fully seated in its base

Check the address matches what is programmed, especially after a replacement

Check whether consecutive addresses went quiet together, because that is a wiring break rather than several device failures

Check terminations at the device and at the previous device on the channel

Swap a known good device of the same type into the address to separate device from wiring

Simplex

Duplicate device#

Scope

Device

Two devices on the channel have the same address. Both answer the same poll and the panel cannot tell them apart.

What to check, in order

Treat this as the cause of any intermittent or wandering faults on that channel, because duplicates present exactly that way

Check any device installed or replaced recently, since a new device left at a default address is the usual source

Pull one suspect device and see whether the duplicate clears, which identifies the pair

Re address the incorrect device and confirm both points report independently

Walk the channel and verify the as built address list against what is actually installed

Simplex

Wrong device#

Scope

Device

The channel detects a device programmed as the wrong device type. The panel expects one thing and something else answered.

What to check, in order

Check the device physically installed against what the point is programmed as

Check whether a head was swapped for a different type, a photo for a heat or a standard for a TrueAlarm

Check the base type matches the head, since sounder and relay bases change what the panel sees

Either fit the correct device or reprogram the point, but do not leave them disagreeing

Test the point after correcting, since device type drives how it alarms

Simplex

Extra Device#

Scope

Device

One or more devices are present on the channel that have not been configured for it. Something is answering that the programming does not know about.

What to check, in order

Identify which address is answering unexpectedly

Check whether a device was added during other trade work and never programmed

Check whether a device was moved from another channel and kept its address

Either add it to the programming or remove it, since an unconfigured device is not supervised or annunciated

Update the as built documentation, because this usually means the record is wrong

Simplex

Short Circuit#

Scope

Device

A short is detected on the channel. Simplex clears this automatically once the short is removed, which makes it useful for confirming a repair.

What to check, in order

Lift the channel at the card and measure to confirm the short is in the field wiring rather than the card

Check for a pinched or skinned conductor at a back box, which is where most shorts live

Check for water in a box or device, particularly exterior and parking structure runs

Split the channel at a reachable midpoint and measure each half, and leave a disconnected half disconnected while you work

Check any device added or disturbed recently

The message clearing by itself confirms the repair, so use that rather than guessing

Simplex

Earth fault#

Scope

Device

A positive or negative earth fault on the channel. Fire alarm wiring has no dedicated ground, so a conductor has found an unintended path to a grounded surface.

What to check, in order

Do not leave the system impaired: notify the authority having jurisdiction and the monitoring company, place the system on test, and post a fire watch if required

Note whether it is the positive or negative side, since Simplex tells you and that halves the search

Check the panel history for when it started and what else happened at that time

Disconnect field channels one at a time to establish whether the fault is on a channel or in the panel

Walk the suspect channel against the usual causes: water at a ceiling device, a pinched conductor, a screw through cable, exterior devices after rain

Split the channel and leave each removed section removed, because faults can sit on more than one section at once

Measure conductor to ground with an ohmmeter before reaching for an insulation tester, and never megger with devices connected

Simplex

Earth Fault Search#

Scope

System

The earth fault search diagnostic is running. This is the panel hunting the fault for you, and system processes are suspended while it does.

What to check, in order

Let it finish and read the progress on the display, because interrupting it wastes the diagnostic

Understand that system processes are suspended during the search, so the system is impaired while it runs

Confirm the monitoring company knows if the search is being run deliberately

Use the result to target the walk rather than starting a manual hunt

Confirm the system returns to normal processing when the search completes

Simplex

Communications Failure#

Scope

System

None of the devices configured on the channel are communicating. The whole channel is dark rather than one device.

What to check, in order

Check the channel wiring at the card first, because losing every device at once points at the head end

Check the card is seated and powered

Check for a short or open right at the start of the run

Check whether recent work disturbed the channel wiring

Treat the entire channel as unprotected and notify accordingly while it is down

Swap the card only after the wiring is proven

Simplex

Controller failure#

Scope

System

The channel cannot detect its controller. Everything on that channel is unavailable.

What to check, in order

Check the controller card is seated and powered

Check the card indicators against the manual for the installed firmware

Check the panel history for when the controller dropped out

Power cycle per the manufacturer procedure rather than pulling cards live

Treat the channel as impaired and notify the authority having jurisdiction and the monitoring company

Escalate to Simplex support rather than swapping cards speculatively

Simplex

Main Overcurrent#

Scope

System

The IDNAC card is drawing more current than it should. Simplex directs you to check for faults on the circuit.

What to check, in order

Check for faults on the circuits fed by that card, which is the manufacturer's own first instruction

Check for a short on any notification circuit, since appliances draw hard into a fault

Disconnect circuits one at a time to find which one is pulling the current

Check for water in an appliance back box on exterior or wet location circuits

Recalculate the load if appliances were added, because an overloaded circuit is a design problem rather than a fault

Correct the overcurrent before attempting to restore power

Simplex

Channel Overcurrent#

Scope

System

A single signaling line circuit is drawing above its rating.

What to check, in order

Identify the channel and what is on it

Check for a short or partial short on that channel

Check for water ingress at devices on the run

Check whether devices were added to the channel without recalculating the load

Disconnect sections progressively to find the section drawing the current

Correct the cause rather than resetting, because the card is protecting itself

Simplex

IDNAC Sig Unpowered#

Scope

System

The IDNAC card is not receiving signal power. Simplex is explicit about the fix: correct the overcurrent, then perform a hardware reset to restore power.

What to check, in order

Find and correct the overcurrent condition first, because the card will not restore while the fault is present

Check the circuits the card feeds for shorts

Perform a hardware reset once the fault is cleared, which is the manufacturer's stated procedure

Confirm the card powers up and the circuits report normal

Test the notification appliances afterwards rather than assuming they came back

Simplex

IDNAC Power Trouble#

Scope

System

The IDNAC card has been damaged, affecting its ability to communicate and power field appliances. Simplex states plainly that the card must be replaced.

What to check, in order

Accept that this one is a replacement rather than a repair, because the manufacturer says so

Treat every notification circuit on that card as out of service and notify the authority having jurisdiction and the monitoring company

Establish whether a fault on the circuits damaged the card, so the replacement does not fail the same way

Check the circuits for shorts or water before fitting a new card

Fully test notification on that card after replacement

Simplex

Smoke Detector Dirty#

Scope

Device

A TrueAlarm sensor's average value has reached the dirty threshold. TrueAlarm compensates for gradual contamination and reports when the compensation runs low.

What to check, in order

Note the address and schedule the clean rather than treating it as an emergency

Check what is around that sensor: construction dust, a kitchen, a dock door, or a return air path

Clean per the manufacturer procedure rather than using compressed air

Run a sensitivity report afterwards and confirm the sensor is back within its listed range

Record the sensitivity result, because that record is what an inspection asks to see

Simplex

Smoke Detector Excessively Dirty#

Scope

Device

The sensor's average value has reached the higher threshold. Compensation has run out and the sensor is now a false alarm risk.

What to check, in order

Treat this as needing action now, since the next event is likely an unwanted alarm out of hours

Clean or replace the sensor per the manufacturer procedure

Run a sensitivity report and confirm the reading is back within the listed range

Replace rather than clean again if it returns quickly

Look hard at the environment, because a sensor that dirties fast is reporting the room rather than itself

Simplex

Almost Dirty#

Scope

Device

A TrueAlarm sensor close to the dirty threshold can be made to report as though it were already dirty. This exists so you can see what is coming while you are already on site.

What to check, in order

Use this deliberately before a maintenance visit to pull up every sensor approaching dirty, so one trip covers them all

Clean the sensors it identifies during the same visit rather than returning later

Run sensitivity reports and record the readings

Remember to turn the feature off afterwards if it was enabled only for planning

Treat a long almost dirty list as an environment question rather than a cleaning schedule question

Simplex

Expired Trouble#

Scope

Device

A CO sensor has reached its expiration. CO sensing elements have a fixed service life and are not listed past it.

What to check, in order

Replace the sensor or its CO element, since an expired element cannot be cleaned or reset back into service

Check the rest of the site for CO sensors of the same vintage, because they were usually installed together

Record the replacement date so the next expiry is planned rather than discovered

Test the replacement per the manufacturer procedure and confirm the point returns to normal

EST and Edwards#

Trouble notes

Signature devices self diagnose; dirty and internal fault states report per device

Map faults occur when the wired layout no longer matches the learned circuit map: look for added, removed, or rewired devices

Riser and audio troubles separate from point troubles on voice systems

Menu concepts

Program and status via the SDU or panel front; mapping is a distinctive EST concept

Test fire groups support walk test

History and status accessible without password; changes gated

Families

EST3, EST4, iO series; Signature series intelligent devices.

Silent Knight#

Trouble notes

Loop troubles report by SLC and point; JumpStart auto programming can mask address mistakes, verify point labels

Ground fault indicated at the main board; isolate by unplugging field circuits

Menu concepts

Front panel programming possible on many models without a laptop

Walk test and fire drill from the test menu

History under the event menu

Families

6000 and IFP series addressable; SK and SD device protocols; part of Honeywell.

Fire Lite#

Trouble notes

Addressable troubles list address and type mismatch separately: type mismatch means the wrong device model answered at that address

NAC troubles per circuit; check the EOL value first (4.7k typical)

Menu concepts

Front panel programming on most models

Read status shows detector chamber values on addressable heads

Walk test silent or audible from the test menu

Families

MS series conventional, ES and MS addressable (LiteSpeed protocol); Honeywell family, shares concepts with Notifier.

Honeywell#

Trouble notes

Identify the actual sub brand and model first; concepts follow the sub brand's line

Shared device protocols exist across sub brands but devices are usually brand locked

Menu concepts

See the specific sub brand entry

Families

Parent of Notifier, Silent Knight, Fire Lite, Gamewell FCI; also Vista and commercial combo panels.

Siemens#

Trouble notes

Device events carry a detailed fault reason (no answer, wrong type, contamination level)

ASA detectors report application specific sensitivity states; contamination reporting is built in

Menu concepts

Person machine interface with access levels; commissioning via Zeus or Cerberus tools

Walk test per zone; event memory extensive

Families

Cerberus PRO and Desigo Fire (FC and FV series), legacy MXL and XLS; FDnet and HNET device buses.

Potter#

Trouble notes

EOL 5.1k on many circuits, different from the 4.7k many techs assume

SLC troubles report per point; check polarity on retrofits, some devices are polarity sensitive

Menu concepts

Front panel menus with USB programming on newer models

Walk test and one person test modes

Families

PFC and IPA addressable series; AFC conventional; also known for sprinkler supervision products.

Gamewell FCI#

Trouble notes

E3 networks distribute intelligence; a network trouble can mimic many point troubles, check network nodes first

Velociti devices share behavior with Notifier FlashScan generation

Menu concepts

Network configuration via CAMWorks; local read status at each node

History per node and network wide

Families

E3 Series, 7100 legacy; S3 Series; Honeywell family, Velociti and CLIP protocols.

Mircom#

Trouble notes

Dual language displays common; troubles list per loop and address

EOL 3.9k typical; verify per model

Menu concepts

Front panel walk test; configurator software for programming

Verify Canadian vs US listing differences on retrofit jobs

Families

FX series addressable, FA conventional; common in Canada, uses AP and CLIP compatible protocols on some lines.

Bosch#

Trouble notes

LSN bus faults report per segment; loop topology matters (T taps limited)

EOL values differ across product generations; check the manual before condemning a circuit

Menu concepts

Programming via RPS or FSP software; limited front panel changes

History and diagnostics from the keypad menus

Families

FPD and Avenar panels; D7024 and FPD 7024 legacy; LSN device bus on newer lines.

More in the LoopWatt reference NEC Article 760 Trouble Families
Field references for other trades Fuel and tanks Solar PV EV charging Battery storage Data center
These notes come from LoopWatt

Reference notes from LoopWatt, the offline field toolkit for fire alarm and life safety technicians. It works with no cell signal, because the sites do not have any.

Get LoopWatt on the App Store

These notes are a field aid, not a substitute for the governing codes, the stamped drawings, the authority having jurisdiction, or manufacturer manuals. Verify against the current documentation for your installed equipment.