Guardian SPGC-220 (single-phase) Fault and Status Codes

Field reference for fuel system and underground storage tank technicians. 14 entries, taken from the DropTubeBuilder app.

These notes come from DropTubeBuilder

Reference notes from DropTubeBuilder, the offline field tool for fuel system technicians who cut overfill drop tubes, build tank charts and chase dispenser faults. It works with no cell signal, because the sites do not have any.

Get DropTubeBuilder on the App Store
Guardian SPGC-220 (single-phase)

Overview

Smart fixed-speed controller for single-phase 200–250 VAC FE Petro (and similar) STPs; also runs DEF-PMA150A/B in DEF Mode (SW2 P6, firmware 0.3.8+). MUST be calibrated before use: close the STP valve, hold Silence/Calibrate ~10 s until 'CAL'/kW alternates, lift a dispenser handle, ~16 s snapshot → 'run'/~100±5%. Reset = hold ~3 s until display blanks. Rotary SW5 stays at 0 unless FE Tech Support says otherwise. With TPI/EVO ATG control, leave Auto Restart, Fault Shutdown, Primary-Secondary and Alternating Circuit switches OFF — the FMS handles them.

Source

Franklin Fueling Systems Single-Phase Guardian Series Controller Installation Guide, doc 223987103

Guardian SPGC-220 (single-phase) · fault

Fault code UL

Underload (dry run)

Likely cause

Motor watts below the calibration value — typically dry running from an empty tank or clogged intake, or a bad calibration.

Action

Check fuel level — under 8", schedule a delivery. Hold Reset until the display blanks. If the STP won't run, use Bypass Mode (SW1 P7) to test, then recalibrate. SW1 P8 (Auto Restart) can auto-retry after UL — but never with TPI.

Guardian SPGC-220 (single-phase) · fault

Fault code Lr

Locked rotor (at startup)

Likely cause

Motor watts above range at start — debris or a damaged PMA rotor, or bad calibration.

Action

Reset. If it recurs: lock out power, pull the extractable, remove the PMA end-bell cap and spin the rotor with an Allen wrench. Binding → replace the PMA and recalibrate; spins free → contact FE Tech Support.

Guardian SPGC-220 (single-phase) · fault

Fault code OL

Overload (while running)

Likely cause

Motor watts above range while running — same causes as Lr.

Action

Same flow as Lr: reset, verify, inspect/spin the rotor, replace PMA if bound, recalibrate (always recalibrate after a PMA change, even same HP).

Guardian SPGC-220 (single-phase) · fault

Fault code LI

Low incoming voltage

Likely cause

Supply below 185 V on L1/L2.

Action

Self-resets once supply is back above 200 V. Verify 200–250 VAC across L1/L2; fix supply wiring if out of range. If connected to an ATG, compare the calibrated voltage (Control Pumps menu) to measured — off by >10 VAC, recalibrate.

Guardian SPGC-220 (single-phase) · fault

Fault code HI

High incoming voltage

Likely cause

Supply above 260 V on L1/L2.

Action

Self-resets below 245 V. Same checks as LI — verify the 200–250 VAC supply.

Guardian SPGC-220 (single-phase) · fault

Fault code OC

Open circuit

Likely cause

Hook signal present but no motor load — broken output wiring/relay, or the PMA thermal overload opened after a locked-rotor event.

Action

Reset. If it recurs: lock out power and check the output connections and motor circuit continuity end-to-end; allow a tripped thermal overload to cool, then recheck.

Guardian SPGC-220 (single-phase) · fault

Fault code Er

Extended run

Likely cause

Ran 60 consecutive minutes with no change in power consumption (stuck hook signal or genuine long-run use).

Action

Check for voltage across the hook terminals with all handles off — if present, have an electrician correct it. For legitimate long-run sites (e.g. generators), SW2 P5 disables Extended Run — but NEVER disable it where the pump must stop for mechanical or electronic line leak detection.

Guardian SPGC-220 (single-phase) · fault

Fault code rEL

Relay fault

Likely cause

PMA is running without a proper hook signal — typically a failed Smart Controller relay contact.

Action

Hold Reset until the code dims. If it recurs, lock out power and replace the SPGC-220 relay board; if it still faults, contact FE Tech Support.

Guardian SPGC-220 (single-phase) · status

Status IdLE Power on, pump off

Idle. If IdLE shows while a dispenser is on, check the hook terminals (120–240 VAC expected) and switch settings; if correct, contact FE Tech Support.

Guardian SPGC-220 (single-phase) · status

Status run Pump running

Alternates 'run' and percent-of-calibration. If it shows run with all dispensers off, power may be present at the hook terminal — contact FE Tech Support.

Guardian SPGC-220 (single-phase) · status

Status unc Uncalibrated

Controller has not been calibrated — perform the calibration procedure before use.

Guardian SPGC-220 (single-phase) · status

Status CAL Calibrating

Alternates 'CAL' and the kW reading of the attached motor during calibration.

Guardian SPGC-220 (single-phase) · configuration

DIP switch settings

SW1 pole 1–5. ON: Address bits 1/2/4/8/16 for Primary-Secondary or Alternating Circuit sets. OFF: —. Factory: OFF. Each controller in a set needs a unique address.

SW1 pole 6. ON: Fault Readout Mode — display steps through the last five faults. OFF: Normal operation. Factory: OFF

SW1 pole 7. ON: Bypass — diagnostics bypassed for 10 minutes (testing only). OFF: Normal operation. Factory: OFF

SW1 pole 8. ON: Auto Restart after an underload (UL) once the hook cycles. OFF: Stay down after UL until manual reset. Factory: OFF. Do NOT use with TPI — the FMS handles restarts.

SW2 pole 1. ON: Fault Shutdown: any fault shuts down ALL controllers in the set (set on Primary only). OFF: A fault stops only the faulted controller. Factory: OFF. Required with Veeder-Root PLLD in Primary-Secondary.

SW2 pole 2. ON: Unused. OFF: —. Factory: ON. Default position is ON.

SW2 pole 3. ON: This unit is the PRIMARY in Primary-Secondary. OFF: Secondary or stand-alone. Factory: OFF

SW2 pole 4. ON: This unit is the Primary of an Alternating Circuit set. OFF: Secondary / stand-alone. Factory: OFF

SW2 pole 5. ON: Disables Extended Run detection. OFF: Extended Run active (60-min limit). Factory: OFF. CAUTION: never disable where the pump must stop for line leak detection.

SW2 pole 6. ON: DEF Mode — DEF-PMA150A/B submersibles only. OFF: Petroleum motors. Factory: OFF. Firmware 0.3.8+. Set BEFORE calibrating DEF units.

SW2 pole 7–8. ON: Unused. OFF: Leave OFF. Factory: OFF

SW5 pole rotary. ON: —. OFF: Leave at position 0. Factory: 0. Moving it off 0 without FE Tech Support direction can break calibration and operation.

These notes come from DropTubeBuilder

Reference notes from DropTubeBuilder, the offline field tool for fuel system technicians who cut overfill drop tubes, build tank charts and chase dispenser faults. It works with no cell signal, because the sites do not have any.

Get DropTubeBuilder on the App Store

These notes are a field aid, not a substitute for the governing codes, the stamped drawings, the authority having jurisdiction, or manufacturer manuals. Verify against the current documentation for your installed equipment.