Get DropTubeBuilder on the App StoreSmart fixed-speed controller for single-phase 200–250 VAC FE Petro (and similar) STPs; also runs DEF-PMA150A/B in DEF Mode (SW2 P6, firmware 0.3.8+). MUST be calibrated before use: close the STP valve, hold Silence/Calibrate ~10 s until 'CAL'/kW alternates, lift a dispenser handle, ~16 s snapshot → 'run'/~100±5%. Reset = hold ~3 s until display blanks. Rotary SW5 stays at 0 unless FE Tech Support says otherwise. With TPI/EVO ATG control, leave Auto Restart, Fault Shutdown, Primary-Secondary and Alternating Circuit switches OFF — the FMS handles them.
Franklin Fueling Systems Single-Phase Guardian Series Controller Installation Guide, doc 223987103
Underload (dry run)
Motor watts below the calibration value — typically dry running from an empty tank or clogged intake, or a bad calibration.
Check fuel level — under 8", schedule a delivery. Hold Reset until the display blanks. If the STP won't run, use Bypass Mode (SW1 P7) to test, then recalibrate. SW1 P8 (Auto Restart) can auto-retry after UL — but never with TPI.
Locked rotor (at startup)
Motor watts above range at start — debris or a damaged PMA rotor, or bad calibration.
Reset. If it recurs: lock out power, pull the extractable, remove the PMA end-bell cap and spin the rotor with an Allen wrench. Binding → replace the PMA and recalibrate; spins free → contact FE Tech Support.
Overload (while running)
Motor watts above range while running — same causes as Lr.
Same flow as Lr: reset, verify, inspect/spin the rotor, replace PMA if bound, recalibrate (always recalibrate after a PMA change, even same HP).
Low incoming voltage
Supply below 185 V on L1/L2.
Self-resets once supply is back above 200 V. Verify 200–250 VAC across L1/L2; fix supply wiring if out of range. If connected to an ATG, compare the calibrated voltage (Control Pumps menu) to measured — off by >10 VAC, recalibrate.
High incoming voltage
Supply above 260 V on L1/L2.
Self-resets below 245 V. Same checks as LI — verify the 200–250 VAC supply.
Open circuit
Hook signal present but no motor load — broken output wiring/relay, or the PMA thermal overload opened after a locked-rotor event.
Reset. If it recurs: lock out power and check the output connections and motor circuit continuity end-to-end; allow a tripped thermal overload to cool, then recheck.
Extended run
Ran 60 consecutive minutes with no change in power consumption (stuck hook signal or genuine long-run use).
Check for voltage across the hook terminals with all handles off — if present, have an electrician correct it. For legitimate long-run sites (e.g. generators), SW2 P5 disables Extended Run — but NEVER disable it where the pump must stop for mechanical or electronic line leak detection.
Relay fault
PMA is running without a proper hook signal — typically a failed Smart Controller relay contact.
Hold Reset until the code dims. If it recurs, lock out power and replace the SPGC-220 relay board; if it still faults, contact FE Tech Support.
Idle. If IdLE shows while a dispenser is on, check the hook terminals (120–240 VAC expected) and switch settings; if correct, contact FE Tech Support.
Alternates 'run' and percent-of-calibration. If it shows run with all dispensers off, power may be present at the hook terminal — contact FE Tech Support.
Controller has not been calibrated — perform the calibration procedure before use.
Alternates 'CAL' and the kW reading of the attached motor during calibration.
SW1 pole 1–5. ON: Address bits 1/2/4/8/16 for Primary-Secondary or Alternating Circuit sets. OFF: —. Factory: OFF. Each controller in a set needs a unique address.
SW1 pole 6. ON: Fault Readout Mode — display steps through the last five faults. OFF: Normal operation. Factory: OFF
SW1 pole 7. ON: Bypass — diagnostics bypassed for 10 minutes (testing only). OFF: Normal operation. Factory: OFF
SW1 pole 8. ON: Auto Restart after an underload (UL) once the hook cycles. OFF: Stay down after UL until manual reset. Factory: OFF. Do NOT use with TPI — the FMS handles restarts.
SW2 pole 1. ON: Fault Shutdown: any fault shuts down ALL controllers in the set (set on Primary only). OFF: A fault stops only the faulted controller. Factory: OFF. Required with Veeder-Root PLLD in Primary-Secondary.
SW2 pole 2. ON: Unused. OFF: —. Factory: ON. Default position is ON.
SW2 pole 3. ON: This unit is the PRIMARY in Primary-Secondary. OFF: Secondary or stand-alone. Factory: OFF
SW2 pole 4. ON: This unit is the Primary of an Alternating Circuit set. OFF: Secondary / stand-alone. Factory: OFF
SW2 pole 5. ON: Disables Extended Run detection. OFF: Extended Run active (60-min limit). Factory: OFF. CAUTION: never disable where the pump must stop for line leak detection.
SW2 pole 6. ON: DEF Mode — DEF-PMA150A/B submersibles only. OFF: Petroleum motors. Factory: OFF. Firmware 0.3.8+. Set BEFORE calibrating DEF units.
SW2 pole 7–8. ON: Unused. OFF: Leave OFF. Factory: OFF
SW5 pole rotary. ON: —. OFF: Leave at position 0. Factory: 0. Moving it off 0 without FE Tech Support direction can break calibration and operation.
Reference notes from DropTubeBuilder, the offline field tool for fuel system technicians who cut overfill drop tubes, build tank charts and chase dispenser faults. It works with no cell signal, because the sites do not have any.
Get DropTubeBuilder on the App StoreThese notes are a field aid, not a substitute for the governing codes, the stamped drawings, the authority having jurisdiction, or manufacturer manuals. Verify against the current documentation for your installed equipment.